The world’s highest power density providing ultimate MW power protection with leading power performance and superior reliability

In this IT intensive world with heavy data traffic driven by cloud, 4G/5G and media streaming applications, IT managers are facing the challenges of increasing rack power density and limited data center space. Delta’s innovative modular UPS technologies provide the answer to customers’ demand for high power density, high power performance, and ultimate availability. The brand-new Delta Modulon DPH series UPS 50-300/500/600kVA achieves the industry’s leading power density of 50kW per module, offering the smallest footprint and best space utilization. The Modulon DPH Series UPS is the ideal modular power protection for MW data centers to achieve total cost of ownership (TCO) optimization.

User-friendly 10" color touch screen; Fully modularized and hot-swappable design

Applications:

DPH series 50-500kVA UPS - Applications


Features

Excellent Power Performance

  • The industry’s leading power density per module at 50kW in 3U space, and the smallest footprint for 500kVA in a single rack and 600kVA in two racks, to achieve the best utilization compared with its peers
  • High AC-AC efficiency up to 96.5% and ECO mode to 99% resulting in marked energy cost savings
  • Green mode featuring a load aggregation function optimizes system efficiency

Ultimate Availability

  • Fully modularized design and hot-swappable key modules ensure Mean Time To Repair (MTTR) close to zero without downtime risk
  • Redundant components and dual CAN bus delivers highest system availability and avoids single point of failure
  • Modular UPS grows with your business by parallel expansion up to 8 units for 4.8MVA of total power capacity

High Manageability

  • User-friendly 10” color touch screen enables easy local UPS management
  • Environment information such as security, water, fire, and temperature can be integrated into the UPS for easy monitoring via the LCD of the UPS
  • If the UPS is equipped with an external battery management system, the battery information can be integrated into the UPS and monitored via the LCD of the UPS

Technical Specifications

Model DPH 300 System
DPH 500 System
DPH 600 System
Power Rating
DPH 300 System 100,150,200,250,300 kVA
100,150,200,250,300 kW
Power Module Quantity : Up to 6 units
DPH 500 System 300,350,400,450,500 * kVA
300,350,400,450,450 kW
Power Module Quantity : Up to 9 units
DPH 600 System 500,550,600 kVA
500,550,600 kW
Power Module Quantity : Up to 12 units
Input
Nominal Voltage 220/380V, 230/400V, 240/415V (3-phase, 4-wire + G)
Voltage Range 176 ~ 276 Vac (full load)
Current Harmonic Distortion < 3% **
Power Factor > 0.99
Frequency Range 40 ~ 70 Hz
Output
Voltage 220/380V, 230/400V, 240/415V (3-phase, 4-wire + G)
Voltage Harmonic Distortion ≤ 0.5% (linear load)
Voltage Regulation ±1% (static)
Frequency 50/60 ± 0.05 Hz
Overload Capability ≤ 125% : 10 minutes
≤ 150% : 1 minute
> 150%: 1 second
Display 10” color touch screen
Interface
Standard RS232 x 1, Parallel port x 4, USB type A x 2, USB type B x 1, MODBUS x 1, Smart slot x 1, REPO x 1, EPO x 1, Input dry contact x 4, Output dry contact x 6, External battery temperature dry contact x 4, External switch/breaker status dry contact x 4, BMS (RJ45) x 1, Ethernet x 1
Optional Relay I/O card, Battery cabinet temperature sensor cable
Conformance
Safety CE
Efficiency
AC-AC Mode Up to 96.5%
ECO Mode 99%
Battery
Nominal Voltage ±240 Vdc
Charge Voltage ±272V (adjustable from 204V to 312V)
Protection of Battery Deep Discharge Yes
Environment
Operating Temperature 0 ~ 40 ℃
Relative Humidity 0 ~ 90% (non-condensing)
Audible Noise (at one meter) DPH 300 System : < 75 dB
DPH 500 System : < 80 dB
DPH 600 System : < 85 dB
IP Protection IP 20
Others
Parallel Redundancy and Expansion Module and system redundancy, Maximum 8 units
Emergency Power Off Remote (default) and local (optional)
Battery Start Yes
Physical
Dimensions (W x D x H) DPH 300 System : 600 x 1100 x 2000 mm
DPH 500 System : 600 x 1100 x 2000 mm
DPH 600 System : 1200 x 1100 x 2000 mm
Weight : UPS System (without power modules) DPH 300 System : 311 kg
DPH 500 System : 317 kg
DPH 600 System : 605 kg
Weight : 50kW Power Module (optional) 36 kg