DPH Series 15-105 kVA (208V)


Introduction

Fully integrated power solutions in one 42U cabinet for small data center applications

The Modulon DPH supports ultimate availability for datacenter operations and provides the benefit of “pay as you go” without over-sizing the UPS. While achieving ultimate availability, the Modulon DPH does not compromise on power efficiency performance. When availabil- ity, efficiency and expanding according to business needs are essential, the Modulon DPH is the ideal UPS system to provide power protection and total cost of ownership (TCO) savings.

Application

Features

High Integration and Space Saving

  • Fully integrated in one 42U cabinet with power supply, battery runtime, static transfer switch and input/output/bypass breakers, not extra solution

Ultimate Availability

  • Fully modularized design and hot-swappable modules for easy deployment and maintenance
  • Redundant aux power and controller design
  • Dual CAN bus to ensure the inherent reliability on signal level
  • Battery module’s LED fuse warning indicators can alert operators in the event of a blown fuse

Excellent Power Performance

  • Industry-leading high power density of power module: 15kVA/kW in 2U height
  • AC-AC conversion efficiency 95% and ECO mode efficiency up to 98.5% with Energy star 2.0 certificated
  • Green mode for effective utilization

High Manageability

  • Environment Management System integration (optional)
  • Power consumption trend calculation
  • Inbuilt Ethernet and RS485 communication interface
  • User-friendly 10” touch panel

Technical Specifications

Model DPH-60K-LV / DPH-105K-LV
Power Rating DPH-60K-LV : 15, 30, 45, 60 kVA/kW

DPH-105K-LV : 15, 30, 45, 60, 75, 90, 105 kVA/kW

Maximum Power Module Q’ty DPH-60K-LV : 4+1 redundancy

DPH-105K-LV : 7+1 redundancy

Maximum Battery Module Q’ty (Inbuilt) DPH-60K-LV : 16 pcs (4 strings)

DPH-105K-LV : N/A

Input
Nominal Voltage 208/120V, 220/127V (3 phase, 4-wire +G)
Voltage Range 166~253 Vac (full load)
iTHD <5% (non-linear)

<3%(linear)*

Power Factor > 0.99
Frequency 50/60 Hz (Auto-Selectable)
Output
Output Voltage 208/120V, 220/127V (3 phase, 4-wire +G)
Voltage Regulation ± 1% (static)
Output Power Factor Unity
THDv < 2% (Linear)

< 5% (Non-linear)

AC-AC Efficiency 95%
ECO Efficiency Up to 98.5%
Overload Capacity ≤125%: 10 min

≤150%: 1 min

>150%: 1 sec

Battery
Nominal Voltage +/- 168Vdc (+/-14 pcs)
Charge Voltage +/- 190Vdc (adjustable from 182Vdc to 196Vdc)
Charge Current 6A Max. per power module
Physical
Dimension (W x D x H) 23.62” x 33.46” x 78.74” (600 x 850 x 2000 mm)
Weight – UPS System DPH-60K-LV: 562.2 lb (255 kg)

DPH-105K-LV: 619.5 lb (281kg)

Weight – Power Module 46.3 lb (21 kg/ 1pc)
Weight – Battery Module 51.8 lb (23.5kg/ 1pc, 1 battery module=9Ah battery x 7pcs)
Environment
Operating Temperature 32 to 104 °F (0 to 40 °C)
Storage Temperature -13 to 167 °F (-25 to 75 °C)
Relative Humidity 5~95% non-condensing
Audible Noise <68 dBA**
Others
Compliance UL 1778, FCC Class A, Energy Start 2.0
Parallel Maximum 4 units
Display 10” Touch Panel
Communication Interface Ethernet, RS485
Modular battery cabinet
Dimension WxDxH 23.62” x 33.46” x 78.74” (600 x 850 x 2000 mm)
Weight w/ Full Battery module : 2123.1 lb (963 kg)

w/o Battery module : 465.2 lb (211 kg)

Maximum Number of Battery Strings 8
Maximum Number of Battery Modules 32

Download

DPH Series 15-105kVA UPS, 208V (Leaflet) – for North and South America (English)

DPH Series 15-105kVA UPS, 208V (User Manual)